7. Test run
177
SMGB0079 rev.0 - 01/2013
7
7.5  Test run procedure from the outdoor unit side
The test run procedure from the outdoor unit side is shown below.
You can set this DIP switch while the power source is ON.
Setting of dip switch
DSW1
1  Test Run
2  COOL/HEAT 
(Setting ON: Heat Operation)
3  COOL / HEAT intermediate season
4  Manual Compressor stop
D A N G E R
•  DonottouchanyotherelectricalcomponentswhileyouaresettingtheswitchesonthePCB.
•  DonotattachordetachtheserviceaccesspanelwhenthepowersourcefortheoutdoorunitisONandthe
outdoorunitisoperating.
•  SetalltheDIPswitchesofDSW1toOFFaftercompletingthetestrun.
 
Operation Dip Switch Setting Operation Remarks
Test Run
  Setting of Operation Mode:
  Cooling: Set DSW1-2 OFF.
  Heating: Set DSW1-2 ON.
  Starting Test Run:
Set  DSW1-1  ON  and  the  ope-
ration is started after  a few ~20 
seconds.
Cooling Heating
  The indoor unit automatically start to 
operate when the test run of the outdoor 
unit is set.
  The ON/OFF operation can be per-
formed from the remote control switch or 
DSW1-1 of the outdoor unit.
  Continuous operation during 2 hours 
is performed without Thermo-OFF.
  N O T E
• TEST RUN operation time can be 
increased  depressing  the  time 
switch in the Remote Control.
• If is setting DSW1-3 ON, cooling/
heating  intermediate  season 
mode is activaded.
•  Take  care that  the  indoor  units  start 
operation in accord  with the test run 
operation of the outdoor unit.
•  The test run is started from the outdo-
or unit and stopped from the remote 
control  switch,  the  test  run  function 
of the remote control switch is cance-
lled. However, the test run function of 
the outdoor unit is not cancelled
•  In  case  that  the  plural  indoor  units 
are connected with  one remote con-
trol switch, all the units start test run 
operation at the same time, therefore, 
turn the power source OFF for the in-
door units not to operate test run. In 
this case, the “TEST RUN” indication 
of the remote control switch may ic-
ker, and this is not abnormal.
•  The setting of  DSW1 is not required 
for the test run from the remote con-
trol switch.
Manual 
OFF of 
Compressor
  Setting: 
Compressor Manual OFF:
Set DSW1-4 ON.
Compressor ON:
Set DSW1-4 OFF.
  When  DSW1-4  is  ON  during  com-
pressor operation, the compressor stops 
to  operate  immediately  and  the  indoor 
unit  is  under  the  condition  of  Thermo-
OFF.
  When  DSW1-4  is  OFF,  the  com-
pressor starts to operate after the can-
cellation of 3-minutes guard.
•  Do  not  repeat  compressor  ON/OFF 
frequently.