7. Test run
180
SMGB0079 rev.0 - 01/2013
21  Does the drain water ow smoothly from the drain pipe? __________
7.6.2  Check list on compressor
CLIENT: MODEL: DATE:
Serial N°: Production date: Checker:
N° Check item Check method Result Remarks
1
Is THM9 correctly connected? 
THM9: Discharge gas thermistor
(1) Is wire of thermistor correctly connected by 
viewing? 
(2) Check to ensure the 7-segment indication of 
Td when comp. is operating.
 Td: Temperature of THM9
2 Is thermistor THM9 disconnected?
(1) Check to ensure that thermistor on the top 
of comp. is correctly mounted by viewing? 
(2) Check to ensure that actually measured 
temp. is the same as the indication during 
check mode.
3 Is current sensor faulty?
(1) Check to ensure that indication A1 and A2 
are 0 during compressor stopping. 
(2) Check to ensure that indication A1 and A2 
are not 0 during compressor running.
4
Is current sensing part on PCB2 
faulty?
5
Is the direction of current sensor 
(CTU, CTV) reverse?
Check the direction => by viewing.
6
Are power source wires, U and 
V inserted correctly into current 
sensor?
Check to ensure that wires are correctly inser-
ted.
7
Is exp. valve (MV1) correctly con-
nected?
Check to ensure that MV1 to CN5A is correctly 
connected.
8
Is exp. valve (MV1) coil correctly 
connected?
Check to ensure that each coil is correctly 
mounted on the valve.
9
Are the refrigeration cycle and 
electrical wiring system incorrectly 
connected?
Check to ensure that refrigerant is owing into 
indoor units by operating one refrigerating cycle 
only from the outdoor unit.
10
Is opening of exp. valve completely 
closed (locked)?
Check the following by the check mode of 
outdoor units.
(1) Liquid pipe temp. (TL) < air intake temp. 
 (Ti) during cooling operation
(2) Liquid pipe temp. (TL) > air intake temp.
 (Ti) during heating operation
11
Is opening of exp. valve fully ope-
ned (locked)?
Check to ensure that liquid pipe temp. is lower 
than air intake temp. of stopping indoor unit 
when other indoor units are operating under 
cooling operation
12
Are the contacts for comp. magnetic 
switch CMC1 faulty?
Check the surface of each contact (L1, L2 and 
L3) by viewing.
13
Is there any voltage abnormality 
among L1-L2, L2-L3 and L3- L1?
Check to ensure that voltage imbalance is sma-
ller than 3%. Please note that power source 
voltage must be within 380V or 220V+10%.
14
Is the comp. oil acidied during 
compressor motor burning?
Check to ensure that the oil color is not black.