10. Servicing
402
SMGB0079 rev.0 - 01/2013
10.4.1.9 Opening electrical box (P plate)
1  Remove the service cover following Removing service cover in this chapter.
2  Unplug all the connectors of the electrical box.
3  Remove 5 screws which x the electrical box and open the P plate turning counter clockwise approximately 90°.
•  Check that the LED201 (red) on the inverter PCB (PCB2) is OFF.
Power Plate
Fixing Screw
2 Fixing Screws
2 Fixing Screws
Upper cover
Power plate
Fixing screw
2 Fixing screws
2 Fixing screws
D A N G E R
•  DONOTtouchelectricalcomponentswhiletheLED201(Red)isONtoavoidelectricalshock.Waituntilthe
LEDturnsoff.
10.4.1.10 Removing Reversing valve coil
1  Remove the service cover, the bottom service cover, the rear cover and the upper cover following Removing service 
cover, Removing bottom service cover and rear cover and Removing upper cover.
2  Disconnect the PCN6 connector on the control PCB of the electrical box.
3  Remove 1 xing screw to remove the reversing valve 
coil.
Reversing valve
Fixing screw for 
Reversing valve
4  When reassembling, perform the procedure in the reverse way of removing.
N O T E
Fixthewiresbyplasticbandstotheoriginalposition.