10. Servicing
417
SMGB0079 rev.0 - 01/2013
10
10.4.2.11 Removing electronic expansion valve coil
1  Remove the service cover, the bottom service cover and the rear cover following Removing service cover and Remo-
ving bottom service cover and rear cover.
2  Disconnect the CN5A connector on the control PCB1 of the electrical box.
3  Hold the coil of the expansion valve and pull out upward.   
It is easier to remove the expansion valve coil if it is rotated 
while pulling it upward.
4  When  reassembling  after  replacing  the  expansion  valve  coil, 
perform  the  procedure  in  the  reverse  way  of  removing.  The 
expansion valve coil is equipped with a lock mechanism. After 
attaching the expansion valve coil, rotate it until the sound of 
locking is heard.
N O T E
Fixthewiresbyplasticbandstotheoriginalposition.
Hold the coil of 
the expansion 
valve and pull 
out upward
Expansion valve coil
Release lock
D A N G E R
DONOTtouchelectricalcomponentswhiletheLED201(Red)orLED1(Red)areONtoavoidelectricalshock.Wait
untiltheLEDsturnoff.
10.4.2.12 Removing solenoid valve coil (SVA)
1  Remove the service cover following Removing service cover.
2  Open the P-mounting plate. Check to ensure the LED201 (Red) of the inverter PCB (PCB2) is OFF.
3  Unplug the connector PCN7 (SVA) on O.U. PCB1.
4  Remove the xing screw, and remove the solenoid valve coil 
(SVA) upward.
5  When reassembling after replacing the solenoid valve coil, per-
form the procedure in the reverse way of removing.
N O T E
Fixthewiresbyplasticbandstotheoriginalposition.
A
Solenoid valve coil (SVA)
Ebox
D A N G E R
DONOTtouchelectricalcomponentswhiletheLED201(Red)orLED1(Red)areONtoavoidelectricalshock.Wait
untiltheLEDsturnoff.