10. Servicing
372
SMGB0079 rev.0 - 01/2013
10.3.3.15 Removing electrical components
Removing control PCB (PCB1) and relay PCB (PCB3)
1  Remove the service cover following Removing service cover.
2  Remove all the wiring connected to the control PCB and the 
relay PCB.
D A N G E R
DO NOT touch electrical components while the LED1
(Red)isONtoavoidelectricalshock.WaituntiltheLED
turnsoff.
3  Remove the 6 holders for each PCB. Clamp the middle part 
of the holders  with long-nose pliers and  remove it toward 
front side.
D A N G E R
DONOTtouchtheelectricalcomponentsonthePCB.
PayattentionnottobendorapplymuchforceontoPCB
inordertoavoidPCBfailure.
Holder
Long-Nose Pliers
Noise Filter
Holder
Noise lter
Long nose pliers
Holder
Printed Circuit Board (PCB1)
Printed Circuit Board (PCB3)
Holder
Removing Inverter module
1  Remove the service cover following Removing service cover.
2  Open the P plate turning counter clockwise approximately 90° following Opening electrical box (P plate).
•  Check that the LED201 (red) on Inverter is OFF when the P plate is opened.
D A N G E R
DONOTtouchelectricalcomponentswhiletheLED201(Red)orLED1(Red)areONtoavoidelectricalshock.
WaituntiltheLEDsturnoff.
3  Remove 4 screws M3, remove the bushes and remove the 
spacers xing the inverter. 
N O T E
Whenmountingagainbesuretoplacethebushesandspa-
cers.
Holder
PCB
Spacer
Inverter PCB
Bush
M3 screw