6. Optional functions
150
SMGB0079 rev.0 - 01/2013
6.1.3  Setting of the optional signals
The optional signals of the outdoor unit are set up from the 
PCB of  the outdoor  unit and  can be  selected  by pushing 
switches PSW1, PSW2 and PSW3.
  N O T E
Beforesettingtheoptionalsignals,mustbecomplied
thefollowingconditions:
• Outdoorunitmustbestopped
• Checkmodemustnotbeselected
• Externaloptionalsignalmustnotbeconnected
If the initial setting has to be modied, the following instruc-
tions must be followed:
1  Set pin 6 of DSW2 to ON. Set pin 4 of DSW1 to ON.  
Because of these settings, the input/output signals se-
lection mode becomes available and the following indi-
cation appears on the 7-segment display.
i 1 1
Input/output 
terminal
Function 
number
   This  example indicates that function number 1  “Fixing 
the heating mode” is set at input 1.
2  By pressing the push switches PSW2 and PSW3, it can 
be  changed  the  input/output  terminal  name.  (See  the 
owchart show in the side).
3 By pressing the push switch PSW1, it can be  changed 
the  function  number.  (See  the  owchart  show  in  the 
side)
4  After  selecting  the  function  number,  return  pin  6  of 
DSW2 to OFF position and pin 4 of DSW1 to OFF.
The  selected  contents  are memorized in the  outdoor  unit 
printed  circuit  board  and  the  function  selection  mode  is 
stopped.  The  memorized  data  is  maintained  even  power 
source  lines  are  disconnected.  The  connecting  details  of 
each function are described, and the required parts are also 
indicated in the section Description of the optional signals 
on this chapter.
Input  setting  1 
CN1, 1-2
1  1
Factory setting
 
PSW1
SET* PSW2 PSW3
 0
~
10
Input  setting  2 
CN1, 2-3
2  2
Factory setting
 
PSW1
SET* PSW2 PSW3
 0
~
10
Input  setting  3 
CN2, 1-2
3  3
Factory setting
 
PSW1
SET* PSW2 PSW3
 0
~
10
Output  setting 
1 CN7, 1-2
o1  1
Factory setting
 
PSW1
SET* PSW2 PSW3
 0
~
10
Output  setting 
2 CN7, 1-3
o2  2
Factory setting
PSW1
SET* PSW2 PSW3
 0
~
10
  (*) Set