10. Servicing
407
SMGB0079 rev.0 - 01/2013
10
10.4.1.16 Removing other electrical components
1  Remove the service cover following Removing service cover in this chapter.
2  Open the P plate turning counter clockwise approximately 90° following Opening electrical box (P plate).
•  Check that the LED201 (red) on Inverter is OFF when the P plate is opened.
D A N G E R
DONOTtouchelectricalcomponentswhiletheLED201(Red)isONtoavoidelectricalshock.Waituntilthe
LEDturnsoff.
CMC
1  Remove all the wiring connected to CMC.
2  Remove 2 screws xing the CMC.
Reactor
1  Remove 4 screws xing the reactor.
Noise lter
1  Remove all the wiring connected to the noise lter.
2  Hold the upper part of the 6 holders with the long nose pliers 
and remove the noise lter.
Holder
Long-Nose Pliers
Noise Filter
Holder
Noise lter
Long nose pliers
Fuse
Noise lter
Reactor
CMC
Holders
Screws
Holders
Screws
N O T E
• Toconnectwiringatreassembling,ensurethattheterminalnumbersandwiringmarkbandcodesaremat-
ched.Ifconnectionsarewrong,thereisthepossibilityofwrongoperationandtocausedamagetoelectrical
parts.
• WhenattachingthePCB,orwhenattachingthepartsattachedtothePCB,payattentionnottoclampanywi-
ringbetweenplatesorelectricalcomponents.