8. Troubleshooting
260
SMGB0079 rev.0 - 01/2013
If you are using a wireless remote control switch with the built-in receiver part of the wall-type indoor unit and you need to
perform the above checking, perform the following procedure:
1 Turn OFF the power supply.
2 Disconnect the connector (CN25) on PWB(M).
3 Connect the PC-ART.
4 Turn ON the power supply.
After nishing the checking, turn OFF the power supply again and reconnect the connectors according to the previous
situation before the checking.
Result
Repeat
From previous page
Press
If there is a next unit
After 7 seconds
After 1 to 5 seconds
Press
(ex.) Indication of unit No. “
1”
Press
After 1 second
Release PCB check
mode
N O T E
• Ifthisindicationcontinuesandthealarmcode“J1”isnotdisplayed,thismeansthateachoneofindoorunit
isnotconnectedtotheremotecontrolswitch.Checkthewiringbetweentheremotecontrolswitchandthe
indoorunit.
• Inthistroubleshootingprocedure,checkingofthefollowingpartsofthePCBisnotavailable.
PCBinindoorunit: relaycircuit,DIPswitch,optioncircuit,fancircuit,protectioncircuit.
PCBinoutdoorunit:relaycircuit,DIPswitch,optioncircuit.
• Ifthistroubleshootingisperformedinthesystemusingthecentralstation,theindicationofthecentralstation
maychangeduringthisprocedure.However,thisisnotabnormal.
• Afterthistroubleshooting,thememoryoftheabnormaloperationoccurrencecounter,whichwasdescribed
before,willbedeleted.