1.5 Checking Using 7-Segment Display
Only an authorized person can check using this method.
(1) Before Checking
Turn ON the main power supply. Wait for more than 20 seconds to start checking.
Checking Items
* Expansion Valve Opening
* Temperature Readings from Thermistors
* Number of Indoor Units Connecting in the Same System
Check the locations of 7-segment and push switches.
AC220~240V is applied to the PCB and electrical parts. Never touch electrical parts and wires without
appropriate personal protective equipment (PPE) when checking.
Check the operating conditions and each part of the refrigerant system temperature condition by 7-segment
display (SEG1) on the service board (3~6.5HP) or outdoor unit PCB (7~12HP) and push switches (PSW).
(A) To start the checking mode: Press PSW2 for 3 seconds;
(B) To move the checking item forward: Press PSW2;
(C) To move the checking item backward: Press PSW3.
(D) To cancel the checking mode: Press PSW2 for 3 seconds.
WARNING
!
PSW3
PSW3
PSW3
PSW3
PSW3
PSW3
PSW3
PSW2
PSW2
PSW2
PSW2
PSW2
PSW2
PSW2
Checking Mode
Normal Mode
PSW2 for 3sec.
PSW2 for 3sec.
ڰڰڰڰڰڰ Indexof
Check Item No.1
ڰڰڰڰڰڰ Information
of Check Item No.1
ڰڰڰڰڰڰ Indexof
Check Item No.2
ڰڰڰڰڰڰ Information
of Check Item No.2
ڰڰڰڰڰڰ Indexof
Last Check Item
ڰڰڰڰڰڰ Information
of Last Check Item