(2) Details of 7-Segment Display
Check Item
Item
Indication Data
No Index Information Contents
Input/Output State of Outdoor Micro-Computer 01
Indicates only for the segments
corresponding to the equipment
Total Capacity of Operation Indoor Unit 02 *1 0
~
199
No. of Control Software 03 *2
Control Software No. in use is
indicated.
No. of Comp. Inverter Software 04 *2
Comp. Inverter Software No. in use
is indicated.
No. of Fan Motor Inverter Software 05 *2
Fan Motor Inverter Software No. in
use is indicated. (If there is only one
fan motor, it indicates the software
No. of fan 2, if there are two fan
motors, it indicates the software No.
of fan 1).
Inverter Order Frequency to Comp. 06 *1 0
~
140(Hz)
Outdoor Fan Step 07 0
~
18(step)
Speed of Outdoor Fan 1 08 *2 0~1000(rpm)
Speed of Outdoor Fan 2 09 *2 0~1000(rpm)
Outdoor Electronic Expansion Valve Opening 10 0
~
100(%)
High Pressure (Discharge Pressure) 11 0.1
~
4.9(MPa)
Low Pressure (Suction Pressure) 12 0.0
~
1.9(MPa)
Discharge Temp. 13 *1 1
~
142 (°C)
Evaporating Temp. (at Outdoor Unit Heat Exchanger) 14 -19
~
80(°C)
Ambient Air Temp. 15 -19
~
80(°C)
Condensing Temp. (at Outdoor Unit Heat Exchanger) 16 -19
~
80(°C)
Comp. Inverter Fin Temp. 17 *1 -19
~
127(°C )
Fan 1 Motor Inverter Fin Temp. 18 *1 -19
~
127(°C)
Fan 2 Motor Inverter Fin Temp. 19 *1 -19
~
127(°C)
Inverter Primary Current 20 *1 0
~
199(A)
Inverter Secondary Current 21 *1 0
~
199(A)
TROUBLESHOOTING