25
INSTALLATION AND OPERATION MANUAL
ENGLISH
1. Prepare locally-supplied copper pipes.
2. Select the piping size with the correct thickness and correct 
material which can have sufcient pressure strength.
3. Select clean copper pipes. Make sure there is no dust and 
moisture inside. Blow the inside of the pipes with oxygen free 
nitrogen to remove any dust and foreign materials before 
connecting pipes.
 NOTE: 
A system with no moisture or oil contamination will give maximum 
performance and lifecycle compared to that of a poorly prepared 
system. Take particular care to ensure all copper piping is clean 
and dry internally.
There is no refrigerant in the cycle of the indoor unit.
 CAUTION:
Cap the end of the pipe when pipe is to be inserted through a 
hole
Do not put pipes on the ground directly without a cap or vinyl tape 
at the end of the pipe
If piping installation is not completed until next day or over a 
longer period of time, braze off the ends of the piping and charge 
with oxygen free nitrogen through a Schrader valve type access 
tting to prevent moisture and particle contamination. 
Do not use insulation material that contains NH3 because it can 
damage cooper pipe material and can be a source of future 
leakage.
Completely insulate both refrigerant gas piping and liquid piping 
between the indoor unit(s) and the outdoor unit.
If not insulated, dew will ocur on the piping surface
 ¡  Fix Unit to the wall
1. Fix the Unit onto the wall as the gure 
indicates. (eld supplied stay)
2. Ensure the foundation so that avoid the 
deforming and noise.
3. In case of prevention from vibration 
transfer to the building, use rubber Mat.
 ¡  Suspended unit
1. Suspend the unit as the drawing 
indicates.
2. Ensure that wall can resist the Outdoor 
unit weight indicated in specication 
label plate.
3. It is recommended to select each foot 
support to bear the full weight of the 
unit (in order to consider stress fatigue 
applied when unit is working too).
 CAUTION:
Pay attention to the following for 
installation:
1. Installation shall ensure that outdoor 
unit will not incline, vibrate, make 
noise or fall down by a blast of 
wind or in an earthquake. Calculate 
quake-resistance strength to 
ensure that installation is strong 
enough against falling. Fix the unit 
with wires (eld supplied) when 
installing in a location without walls 
or windbreak and likely exposed to 
a blast of wind.
2. To use a vibration-proof mat, x four 
places to the front and back.
 ¡ Installing location where the unit will be exposed to strong wind.
Follow the instructions below to install 
on the rooftop or a location without 
surrounding buildings, where strong 
wind is expected against the product.
1. Choose a location where the outlet 
or inlet side of the product will not be 
exposed to strong wind.
2. When the outlet is exposed to strong 
wind: 
Direct strong wind may cause lack 
of air ow and adversely affect to the 
operation.
 CAUTION:
Excessive strong wind against the outdoor 
unit outlet may cause inverse rotation and 
damage the fan and motor.
11  REFRIGERANT PIPING & REFRIGERANT CHARGE 
11.1.  PIPING MATERIALS
Mark Dimension
Model
4~6HVRNS1E 
3HVRNME
4~6H(V)RNM1E
A (mm) 529 1109
Wall bracket (*)
Anchor Bolts (*)
(*) Field supplied
Rubber 
Material 
(Field 
Supplied)
PMML0197_r0_04-10.indb   25 08/07/2010   9:20:35