4 Control system
Safety protection and control
SMGB0137 rev.0 - 05/2021
90
4.11 Safety protection and control
Setting control and safety devices for indoor units
Model RCI-FSR RPI (L/H)
RCIM-
FSRE
RPK RCD RPC-FSR
RPI-(8.0/10.0)
FSN3E(-f)
RPI-(16.0/20.0)
FSN3PE(-f)”
RPF(I)
For the
evaporator fan
motor: internal
thermostat
Switch
o
ºC 80 ±4 (*) 110±10 100±4 (*) 100±4 (*) 100±4 (*)
100-10 /
+15 (*)
140±10 130±5
Switch
on
ºC 90±10 90±15 93±15
For the control
circuit: fuse
capacity
- A 5 5 5 5 5 5 10 5
Freeze
Protection
Thermostat
Cut-Out ºC 0 - 0 0 0 0 - -
Cut-in ºC 14 - 14 14 14 11 - -
Thermostat
dierential
- ºC 2 - 2 2 2 2 - -
? NOTE
(*) Chip Ceramic PTC (Autoreset, non-adjustable)