5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
142
5.2.3 Optional functions for PC-ARH1E remote controls
Item Optional function
Individual
Setting
Settings Setting conditions Description
b1
Heating temperature
compensation
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
RPI-FSN3E(P)E(-f)
RPK-FSR(H)M
○
00
Normal (factory setting)
(Setting Temperature + 4 ºC)
This function is used to adjust the
temperature dierence between the
temperature read by the inlet sensor
and the real room temperature.
This is useful when the inlet air
thermistor is not placed inside the
indoor unit or due to uneven heat
load.
? NOTE
• The “02”, “03”, “04” settings may
not be available depending on
the type of indoor unit.
• This setting shall be performed
separately for each indoor unit,
even in case that multiple indoor
units are connected to one
remote controller.
01
No compensation
(Setting Temperature)
02 Setting Temperature + 2 ºC
03 Setting Temperature + 3 ºC
04 Setting Temperature + 1 ºC
Heating temperature
compensation
Models:
RPF(I)-FSN2E
○
00
RPF(I)-FSN2E: Normal
(factory setting)
(Setting Temperature + 2 ºC)
01
No compensation
(Setting Temperature)
02 Setting Temperature + 2 ºC
b2
Circulation function
at heating
Thermo-OFF
○
00
Function disabled
(factory setting)
This function keeps the fan running
during the Thermo-OFF sequence,
at the fan speed set on the remote
control switch, to prevent the
stratication of air in the room.
01 Function enabled
b3
Not Used -
00
- Use at 00 conditions
01
b4
Change of lter
cleaning period
○
00 Standard (1200 hours)
This function is used to modify the
period of operation after which the
air lter cleaning indication is shown
in the remote control.
For RPK-FSR(H)M models, the
factory setting is b4=00: Standard
setting 200 hours.
01 100 hours
02
1200 hours
(factory setting)
03 2500 hours
04 No indication
b5
Locking of operation
mode
(Not available for
models KPI-E4)
×
00
Function disabled
(factory setting)
This function prevents the
modication of the operation mode
of the unit from the remote controller
and from central controls, once it
has been selected.
01 Function enabled
b6
Locking of setting
temperature
×
00
Function disabled
(factory setting)
This function prevents the
modication of the setting
temperature of the unit from the
remote controller and from central
controls, once it has been selected.
01 Function enabled
b7
Setting operation
mode as cooling
only.
(Not available for
models KPI-E4)
×
00
Function disabled
(factory setting)
This function is used to limit the
operation mode to cooling only and
to prevent heating mode from being
enabled.
01 Function enabled
b8
Automatic COOL/
HEAT operation.
(Not available for
models KPI-E4)
×
00 Function disabled (factory setting)
This function enables the selection
of Auto cool/heat operation mode.
If the function is not activated, Auto
cool/heat mode cannot be selected
on the remote control switch.
01 Function enabled