5 Optional functions
Indoor units input and output signals
SMGB0137 rev.0 - 05/2021
100
Function 2: remote switching OFF of the unit (pulse signal input)
On-screen display: 05.
This is an optional remote o󰀨 signal that uses the pulse signal.
If a signal is input during the stoppage of the system, it remains unchanged.
Connect the wiring and use the materials as indicated in “5.1.1 Available ports”. (Example: terminal 1 and 2 of CN3)
ON
X1
OFF
X2
CN3
X1
X2
3
2
1
3
2
1
3P Connector
Indoor unit PCB
Control circuit
Power
supply
? NOTE
The pulse range shall be 200 ms or more.
A time chart with the uses of functions 2 is shown below.
Control using the
RCS
CN3 signal
(Terminal 2
and 3)
Time
Unit operation
CN3 signal
(Terminal 1
and 2)
ON
ON
ON
OFF
OFF
OFF
? NOTE
The collection of signals during the rst 10 seconds after connecting the power supply is not available due to component initialization.
Do not change the signal in this period.
Wired controller or receiver kit is required for this function.
If multiple indoor units are connected to the same transition wiring of the controller, input the signal to any of these indoor units.
When the transition wiring is not used in the twin, triple and quad combinations for simultaneous operation, input the signal to the
main indoor unit.