5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
108
Element Optional function
Individual
setting
Settings
Setting conditions Description
b7
Setting operation mode as
cooling only
(Not available for models
KPI-E4)
X
00
Function disabled
(factory setting)
This function is used to limit the
operation mode to cooling only
and to prevent heating mode
from being enabled.
01
Function enabled
b8
Automatic COOL/HEAT
operation
(Not available for models
KPI-E4)
X
00
Function disabled (factory setting)
This function enables the
selection of Auto cool/heat
operation mode. If the function
is not activated, Auto cool/heat
mode cannot be selected on the
remote control switch.
01
Function enabled
b9
Locking of fan speed
setting
(Not available for models
KPI-E4)
X
00
Function disabled
(factory setting)
This function prevents the
modication of the fan speed
of the unit from the remote
controller and from central
controls, once it has been
selected.
01
Function enabled
bA
Not available X
“- -”
permanent
Not available –
bb
Cooling setting
temperature correction
O
00
No compensation (factory setting)
This function decreases the
setting temperature and is
used to produce longer cooling
periods.
01
Setting temperature decreased by 1
ºC
02
Setting temperature decreased by 2
ºC
bC
Not used –
00
- Use at 00 conditions
01
bd
Not used –
00
- Use at 00 conditions
01
bE
Not used –
00
- Use at 00 conditions
01
C1
Not used –
00
- Use at 00 conditions
01
C2
Not available –
“- -”
permanent
- –
C3
Not used
–
00
- Use at 00 conditions
01
Only for DX-Interface,
KPI-E4E and KPI-X4E:
Fan stoppage delay
00
Function disabled
(factory setting)
This function keeps the fan in
operation for 60 minutes after
stop of the KPI unit or DX-
Interface.
01
60 minutes
C4
Drain pump operation in
heating mode
O
00
Function disabled
(factory setting)
This function is used to activate
the drain pump in heating mode.
Only for models with drain
pump.
01
Function enabled