5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
120
Element Optional function
Individual
setting
Settings
Setting conditions Description
L5
Louvre swing operation
during energy-saving
forced Thermo-OFF
O
00
Function disabled
(factory setting)
This function is used to enabled
the setting of function L3.
01
Function enabled
L6
Not used -
00
- Use at 00 conditions
01
L7
Not available
“- -”
permanent
L8
Not used -
00
- Use at 00 conditions
01
L9
Not used -
00
- Use at 00 conditions
01
LA
Not used -
00
- Use at 00 conditions
01
Lb
Not used -
00
- Use at 00 conditions
01
P1
Setting temperature in 0.5
ºC steps
X
00
Enabled (0.5 °C steps)
(factory setting)
This function is used to dene 
whether setting temperature is
adjusted in 0.5 ºC steps (when
set to “00”) or in 1 ºC steps
(when set to “01”).
This setting also determines
whether the resolution of
temperature di󰀨erential of the 
thermistor is 0.5 ºC (when set to
“00”) or 1 ºC (when set to “01”).
01
Disabled (1 °C steps)
P2
Not used -
00
- Use at 00 conditions
01
P3
Temperature sensor
displayed
X
00
Inlet air thermistor (Tin)
This function is used to
select the thermistor whose
temperature is shown when
function P4 is set to 01.
01
Outdoor air thermistor (Tout)
02
Remote controller thermistor (RCS)
03
Remote sensor (THM4)
P4
Display of sensor
temperature
X
00
Hidden
This function is used to display
the temperature of the sensor
selected with function P3.
01
Shown
P5
Display of setting
temperature when
operation mode is Fan
X
00
Shown
This function is used to hide the
display of setting temperature
during operation in fan mode.
01
Hidden
P6
Operation of the ECO
button
X
00
ECO button enabled (factory setting)
The operation of ECO button is
disabled when P6 is set to 01
01
ECO button disabled
P7
Prohibition of menu
screen transition
X
00
Function disabled
(factory setting)
This function is used to prohibit
the access to the menu screens.
The text "Display disabled" 
appears on screen instead.
01
Function enabled
P8
Not used -
00
- Use at 00 conditions
01
P9
Not used -
00
- Use at 00 conditions
01
PA
Daylight saving time X
00
1 hour
This function is used to set the
amount of adjustment when
daylight saving time is applied.
01
2 hours