5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
123
5
Element Optional function
Individual
setting
Settings
Setting conditions Description
rb
Minimum operation time
to allow the change of
operation mode in auto
cooling/heating mode with
dual set point
X
00
Disabled
This function is used to dene
a minimum time of operation
in a given mode, in order to
avoid too frequent changes of
operation mode.
Operation mode does not
change until the minimum
transition time passes, even if
the room temperature reaches
the setpoint to shift to the other
operation mode.
01
10 minutes
02
20 minutes
03
30 minutes
04
40 minutes
05
50 minutes
06
60 minutes
07
70 minutes
08
80 minutes
09
90 minutes
10
100 minutes
11
110 minutes
12
120 minutes
rC
Maximum outdoor
temperature to allow
operation mode switch to
heating in auto cooling/
heating with dual set point
X
00
Disabled
If outdoor ambient temperature
is higher than rC, there is no
mode transition to heating
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from cooling to heating.
01
20.0 ºC
02
21.0 ºC
03
22.0 ºC
·
·
·
·
·
·
21
40.0 ºC
22
0.0 ºC
23
1.0 ºC
24
2.0 ºC
·
·
·
·
·
·
41
19.0 ºC
rd
Minimum outdoor
temperature to allow
operation mode switch to
cooling in auto cooling/
heating with dual set point
X
00
Disabled
If outdoor ambient temperature
is lower than rd, there is no
mode transition to cooling
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from heating to cooling.
01
10.0 ºC
02
11.0 ºC
03
12.0 ºC
·
·
·
·
·
·
31
40.0 ºC
32
-20.0 ºC
33
-19.0 ºC
34
-18.0 ºC
·
·
·
·
·
·
61
9.0 ºC