7 Servicing
RCD-(0.8-6.0)FSR - 2-way cassette
SMGB0137 rev.0 - 05/2021
202
Method of Attaching Air Filter
a. Place the air lter on  the top of the air inlet at grille.
b.  Hold the trim of the air lter.
Air inlet at grille
c. Insert the hooks into the holes on the air lter.
P-AP90DNA
P-AP160DNA
Front side
Hook
Rear side
Hole on the air lter
Hook
Hook
Front side
Hook
Rear side
Hole on the air lter
d.  Slide the air lter only on the front side in order to 
lock the hooks.
P-AP90DNA
P-AP160DNA
After sliding
Direction of slide
Large size lter
Small size lter
After sliding
e. Attach the air lter on the rear side.
3 Remove the air inlet at grille
Remove the supporting string from the air panel.
• 
Open the air inlet at grille at an approximately 40° angle from the air panel surface.
• 
Tilting the air inlet at grille, lift it up to remove it.
? NOTE
Although the air inlet at grille can be opened up to 90°, it cannot be removed from the air panel at the angle. Tilt it at a 40° angle when
removing it.
40
o
Air inlet at grille
Air Panel
Ceiling
Tilting the air inlet at grille, lift it up to remove it.
Attach the air inlet at grille in the reverse procedure for removing. The supporting string is attached to the side plate.