3 Electrical and control settings
Unit electrical wiring and connection
SMGB0137 rev.0 - 05/2021
41
3
Electrical connection
Maketheconnectionbetweentheindoorunitandtheairpanel.
? NOTE
• Topreventthescrewsfromfallingfromtheterminalbox,donotremovethemcompletely,holdontotheterminalandcheckthatthe
screw is secure through the hole in the terminal.
• Usethefollowingscrewsfortheterminalbox:
- M4 screw for the power supply.
- M3.5 screw for the operating line.
Electricalbox
Remote control switch cable
Control cable
Power source cable
Indoor unit
Air panel
Cable for auto swing motor
Wire clamp
Electricalbox
Wire clamp
Air panel
Indoor unit
Connector (CN17)
Earth
screw
Control cable
Remote control
switch cable
Power
source cable
PCB
Cable for auto
swing motor
Terminal Board 1 Terminal Board 2
-
S/NR/L1
Terminal board for Power source cable
AB
Terminal board for Control source cable
Followthestepsbelowtoconnecttheremotecontrolcableortheoptionalextensionwire:
1 Passthecablethroughtheknock-outholeinthecabinet.
2 Connect the cable to terminals A and B of the terminal strip (TB2).
3 Tighten the screw on terminals A and B.
4 Checkthatthecablesarecorrectlysecured.
Followthestepsbelowtoconnectthepowercablestotheterminalstrip(TB1):
! CAUTION
• Toconnectapowersupplywithneutral,connectthecablestoterminalsL1andNontheterminalstrip(TB1).
• Toconnectapowersupplywithoutneutral:maketheconnectiontoterminalsL1andL2ontheterminalstrip(TB1).
1 Where necessary, loosen the screws on terminals L1 and N or L1 and L2, as applicable, on the terminal strip (TB1).
2 Connect the power cables to terminals L1 and N or L1 and L2, as applicable.
3 Tighten the screws on terminals L1 and N or L1 and L2, as applicable.
4 Checkthatthecablesarecorrectlysecured.
Follow the steps below to connect the communication cables between the outdoor and indoor unit to the terminal strip
(TB2):
1 Where necessary, loosen the screws on terminals 1 and 2 on the terminal strip (TB2).
2 Connect the communication cables to terminals 1 and 2.
3 Tighten the screw on terminals 1 and 2.
4 Checkthatthecablesarecorrectlysecured.