Step-by-Step Basic Installation
Inverter Mounting
and Installation
2–20
Please use the terminal arrangement below corresponding to your inverter model.
NOTE: An inverter powered by a portable power generator may receive a distorted
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).
CAUTION: Be sure that the input voltage matches the inverter specifications:
• Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFEF/NFU models
• Three phase 200 to 240V 50/60Hz (above 2.2kW) for LFU models
• Three phase 380 to 480 V 50/60Hz for HFEF models
CAUTION: Be sure not to power a three-phase-only inverter with single phase power.
Otherwise, there is the possibility of damage to the inverter and the danger of fire.
Inverter models SJ200–002NFEF/NFU to –005NFEF/NFU
Inverter models SJ200–007NFEF to –022NFEF,
–007NFU to –037LFU, –004HFEF/HFU to –040HFEF/HFU
Jumper
Jumper
Chassis
Ground
Chassis
Ground
RB
U/T1
RB
U
/T1
V
/T2
W
/T3
Inverter models SJ200–055HFEF/HFU, –075HFEF/HFU
Jumper
U/T1
V/T2
W/T3
Chassis
Ground
+1 +
L1 L2
+1 +
L1 L2 N/L3
L1 L2 L3
NFEF, NFU
LFU, HFEF, HFU
L3
+1 +
RB
L1 L2
V/T2
W/T3
N/L3
U/T1
V/T2
W/T3