Chapter 6 Interface with the Inverter
6 - 1
6.1 Inverter Settings Related to the Easy Sequence Function
The following table lists the inverter settings related to the easy sequence function.
Item
Category
Terminal name
Variable notation
in program
Related function
code
Variable/
terminal use condition
Operation
switching
Selection of easy sequence function - A017 -
Program run signal PRG (FW terminal) - A017
The PRG terminal is
enabled when A017 = 01.
(The FW function is
disabled.)
General-purpose input
contacts (8 contacts)
Intelligent input
terminals 1 to 8
X (00) to X (07)
Xw
C001 to C008
Intelligent output
terminals 11 to 15
C021 to C025
General-purpose
output contacts (6
contacts)
Intelligent relay output
terminals AL0 to AL2
Y (00) to Y (05)
Yw
C026
Function code settings are
required.
O terminal XA (0) -
OI terminal XA (1) -
General-purpose
analog inputs
(3 terminals)
O2 terminal XA (2) -
No setting is required.
FM terminal YA (0) C027
AM terminal YA (1) C028
Input/
output
switching
General-purpose
analog outputs
(3 terminals)
AMI terminal YA (2) C029
Function code settings are
required.
Frequency command selection SET-Freq A001
Related variables are valid
only when A001 = 07.
Operation command selection
FW, RV
STA, STP, F/R
A002
Related variables are valid
only when A002 = 01.
Command
switching
Acceleration/deceleration input selection
ACCEL
DECEL
P031
Related variables are valid
only when P031 = 03.
Other User-defined variables (32 variables) U (00) to U (31) P100 to P131
The variables can be
redefined by using the
digital operator or EzSQ.