Chapter 8 Appendix
8 - 1
8.1 Inverter Parameters and Available Settings
The tables below list the parameters and ranges of settings available for updating with the chg param
instruction.
(1) F parameters
Display
code
Function name Range of setting
Minimum
unit
Setting during
operation
(allowed or not)
Updating during
operation
(allowed or not)
F001 Output frequency setting Do not use
F002 Acceleration (1) time setting 1 to 360000 0.01 (s)
F202
Acceleration (1) time setting,
2nd motor
1 to 360000 0.01 (s)
F302
Acceleration (1) time setting,
3rd motor
1 to 360000 0.01 (s)
F003 Deceleration (1) time setting 1 to 360000 0.01 (s)
F203
Deceleration (1) time setting,
2nd motor
1 to 360000 0.01 (s)
F303
Deceleration (1) time setting,
3rd motor
1 to 360000 0.01 (s)
F004 Keypad Run key routing 0 (forward rotation), 1 (reverse rotation) × ×
(2) A parameters
Display
code
Function name Range of setting
Minimum
unit
Setting during
operation
(allowed or not)
Updating during
operation
(allowed or not)
A001 Frequency source setting
0 (keypad potentiometer), 1 (control circuit terminal block),
2 (digital operator), 3 (RS485), 4 (option 1), 5 (option 2),
6 (pulse-string input), 7 (easy sequence),
10 (operation function result)
× ×
A002 Run command source setting
1 (control circuit terminal block), 2 (digital operator),
3 (RS485), 4 (option 1), 5 (option 2)
× ×
A003 Base frequency setting 30 to "maximum frequency " 1 (Hz) × ×
A203
Base frequency setting, 2nd
motor
30 to "maximum frequency, 2nd motor"
1 (Hz) × ×
A303
Base frequency setting, 3rd
motor
30 to "maximum frequency, 3rd motor"
1 (Hz) × ×
A004 Maximum frequency setting 30 to 400 1 (Hz) × ×
A204
Maximum frequency setting,
2nd motor
30 to 400
1 (Hz) × ×
A304
Maximum frequency setting,
3rd motor
30 to 400
1 (Hz) × ×
A005 [AT] selection
0 (switching between O and OI terminals), 1 (switching
between O and O2 terminals), 2 (switching between O
terminal and keypad potentiometer), 3 (switching between
OI terminal and keypad potentiometer), 4 (switching
between O2 and keypad potentiometer)
× ×
A006 [O2] selection
0 (single), 1 (auxiliary frequency input via O and OI
terminals) (nonreversible), 2 (auxiliary frequency input via
O and OI terminals) (reversible), 3 (disabling O2 terminal)
× ×
A011
[O]-[L] input active range start
frequency
0 to 40000
0.01 (Hz) ×
A012
[O]-[L] input active range end
frequency
0 to 40000
0.01 (Hz) ×
A013
[O]-[L] input active range start
voltage
0. to "[O]-[L] input active range end voltage"
1 (%) ×
A014
[O]-[L] input active range end
voltage
"[O]-[L] input active range start voltage" to 100
1 (%) ×
A015
[O]-[L] input start frequency
enable
00 (external start frequency), 01 (0 Hz)
×
A016
External frequency filter time
const.
1. to 30. or 31 (500 ms filter ±0.1 Hz with hysteresis)
×
A017
Easy-sequence function
selection
0 (disabling), 1 (enabling)
× ×
A019 Multispeed operation selection
0 (binary: 16 speeds selectable with 4 terminals), 1 (bit: 8
speeds selectable with 7 terminals)
× ×
A020 Multistage frequency setting 0 to “maximum frequency” 0.01 (Hz)
A220
Multistage frequency setting,
2nd motor
0 to “maximum frequency, 2nd motor”
0.01 (Hz)
A320
Multistage frequency setting,
3rd motor
0 to “maximum frequency, 3rd motor”
0.01 (Hz)