Chapter 8 Appendix
8 - 4
(2) A parameters
Display
code
Function name Range of setting
Minimum
unit
Setting during
operation
(allowed or not)
Updating during
operation
(allowed or not)
A098 Deceleration curve setting
0 (linear), 1 (S curve), 2 (U curve),
3 (inverted-U curve), 4 (EL-S curve)
− × ×
A101
[OI]-[L] input active range start
frequency
0 to 40000 0.01 (Hz) × ○
A102
[OI]-[L] input active range end
frequency
0 to 40000 0.01 (Hz) × ○
A103
[OI]-[L] input active range start
current
0 to "[OI]-[L] input active range end current" 1 (%) × ○
A104
[OI]-[L] input active range end
current
"[OI]-[L] input active range start current" to 100 1 (%) × ○
A105
[OI]-[L] input start frequency
enable
0 (external start frequency), 1 (0 Hz) − × ○
A111
[O2]-[L] input active range start
frequency
-40000 to 40000 0.01 (Hz) × ○
A112
[O2]-[L] input active range end
frequency
-40000 to 40000 0.01 (Hz) × ○
A113
[O2]-[L] input active range start
voltage
-100 to 02 end-frequency rate 1 (%) × ○
A114
[O2]-[L] input active range end
voltage
"02 start-frequency rate" to 100 1 (%) × ○
A131
Acceleration curve constants
setting
1 (smallest swelling) to 10 (largest swelling) − × ○
A132
Deceleration curve constants
setting
1 (smallest swelling) to 10 (largest swelling) − × ○
A141
Operation-target frequency
selection 1
0 (digital operator), 1 (keypad potentiometer), 2 (input
via O), 3 (input via OI), 4 (external communication),
5 (option 1), 6 (option 2), 7 (pulse-string frequency input)
− × ○
A142
Operation-target frequency
selection 2
0 (digital operator), 1 (keypad potentiometer), 2 (input
via O), 3 (input via OI), 4 (external communication), 5
(option 1), 6 (option 2), 7 (pulse-string frequency input)
− × ○
A143 Operator selection
0 (addition: A141 + A142), 1 (subtraction: A141 - A142),
2 (multiplication: A141 x A142)
− × ○
A145 Frequency to be added 0 to 40000 0.01 (Hz) × ○
A146
Sign of the frequency to be
added
0 (frequency command + A145),
1 (frequency command - A145)
− × ○
A150 EL-S-curve acceleration ratio 1 0 to 50 1 (%) × ×
A151 EL-S-curve acceleration ratio 2 0 to 50 1 (%) × ×
A152 EL-S-curve deceleration ratio 1 0 to 50 1 (%) × ×
A153 EL-S-curve deceleration ratio 2 0 to 50 1 (%) × ×
*1
Display
code
Inverter
capacity
Setting range
Under 55(kW) 0 to 100
75 to 132(kW) 0 to 80
A054/A057
Over 160(kW) 0 to 35
*2
Display
code
Inverter
capacity
Setting range
Under 55(kW) 5 to 150
75 to 132(kW) 5 to 100
A059
Over 160(kW) 5 to 30