Chapter 8 Appendix
8 - 11
(4) C parameters
Display
code
Function name Range of setting
Minimum
unit
Setting during
operation
(allowed or not)
Updating during
operation
(allowed or not)
C041 Overload level setting 0 to 2000 0.1 (%) ×
C042
Frequency arrival setting for
accel.
0 to 40000 0.01 (Hz) ×
C043
Frequency arrival setting for
decel.
0 to 40000 0.01 (Hz) ×
C044 PID deviation level setting 0 to 1000 0.1 (%) ×
C045
Frequency arrival setting for
acceleration (2)
0 to 40000 0.01 (Hz) ×
C046
Frequency arrival setting for
deceleration (2)
0 to 40000 0.01 (Hz) ×
C052 Maximum PID feedback data 0 to 1000 0.1 (%) ×
C053 Minimum PID feedback data 0 to 1000 0.1 (%) ×
C055
Over-torque (forward-driving)
level setting
*7 1 (%) ×
C056
Over-torque (reverse
regenerating) level setting
*7 1 (%) ×
C057
Over-torque (reverse driving)
level setting
*7 1 (%) ×
C058
Over-torque (forward
regenerating) level setting
*7 1 (%) ×
C061
Electronic thermal warning level
setting
0 to 100 1 (%) ×
C062 Alarm code output 0 (disabling), 1 (3 bits), 2 (4 bits) ×
C063 Zero speed detection level 0 to 1000 0.1 (Hz) ×
C064 Heat sink overheat warning level 0 to 200 1 () ×
C071 Communication speed selection
2 (loopback test), 3 (2,400 bps), 4 (4,800 bps), 5 (9,600
bps), 6 (19,200 bps)
×
C072 Node allocation 1 to 32 ×
C073
Communication data length
selection
7 (7 bits), 8 (8 bits) ×
C074 Communication parity selection 0 (no parity), 1 (even parity), 2 (odd parity) ×
C075 Communication stop bit selection 1 (1 bit), 2 (2 bits) ×
C076
Selection of the operation after
communication error
0 (tripping), 1 (tripping after decelerating and stopping
the motor), 2 (ignoring errors), 3 (stopping the motor
after free-running), 4 (decelerating and stopping the
motor)
×
C077
Communication timeout limit
before tripping
0 to 9999 0.01 (s) ×
C078 Communication wait time 0 to 1000 1 (ms) ×
C079 Communication mode selection 0(ASCII), 1(Modbus-RTU) ×
C081 [O] input span calibration 0 to 65530
C082 [OI] input span calibration 0 to 65530
C083 [O2] input span calibration 0 to 65530
C085 Thermistor input tuning 0 to 10000
C091 Debug mode enable
(Do not change this parameter, which is intended for
factory adjustment.)
× ×
C101
Up/Down memory mode
selection
0 (not storing the frequency data),
1 (storing the frequency data)
×
C102 Reset mode selection
0 (resetting the trip when RS is on), 1 (resetting the trip
when RS is off), 2 (enabling resetting only upon tripping
[resetting when RS is on]),3 (resetting only trip)
C103 Restart mode after reset
0 (starting with 0 Hz), 1 (starting with matching
frequency), 2 (restarting with active matching frequency)
×
C105 FM gain adjustment 50 to 200 1 (%)
C106 AM gain adjustment 50 to 200 1 (%)
C107 AMI gain adjustment 50 to 200 1 (%)
C109 AM bias adjustment 0. to 100 1 (%)
C110 AMI bias adjustment 0. to 100 1 (%)
C111 Overload setting (2) 0 to 2000 0.1 (%) ×
C121 [O] input zero calibration 0 to 65530
C122 [OI] input zero calibration 0 to 65530
C123 [O2] input zero calibration 0 to 65530
C130 Output 11 on-delay time 0 to 1000 0.1 (s) ×
C131 Output 11 off-delay time 0 to 1000 0.1 (s) ×
C132 Output 12 on-delay time 0 to 1000 0.1 (s) ×
C133 Output 12 off-delay time 0 to 1000 0.1 (s) ×