MAN0530 Issue 15 - 07/17 Searchline Excel
2104M0506
37=Ethylene(%UEGm)
38=Propylene(%UEGm)
39=Butadiene(%UEGm)
40=Ethanol(%UEGm)
41=Methanol(%UEGm)
Gas Units Gas Units LELm,
PPMm,
UEGm, or
VVm
%LEL (Cross-Duct only)
Effective Full Scale Gas Full Scale 0.1 100000 0.05
Show Cong
Thisoptiondisplaysthecongurationparameterstheusercansetinthesamewayasforthe
Show Gas option.Thecongurablesettingsand values are shown in the following table:
CongurationParameters Display Text Min Value Max Value Step Size
Default
Values
Protocol Address Digital Address 0 255 1 0
Time to Block
Block Warn Time
5s 600s* 5s 30s
Time to Fault
Block Fault Time
0s 600s 5s 120s
Max Response
Maximum T90
1s 60s 1s 60s
Analogue Style
Analogue Mode
Alarm or Continuous C
Inhibit Current
Inhibit mA
0mA 3mA 0.05mA 2.0mA
Block Current
Blocked mA
0mA 4mA 0.05mA 2.5mA
Low Signal Current
Low Signal mA
0mA 4mA 0.05mA 3.0mA
Low Signal Level
Low Signal %
0% 90% 1% 33%
Alarm Threshold
Alarm Threshold
10% 100% 1% 20%
Report fault due to blockage
RPRT Blocked Fault
Enable or Disable E
* To comply with FM performance approval, the maximum value for Time to Block is 200 s.
Show Install
This option displays the installation conguration parameters in the same way as for the
Show Gas option.Thecongurablesettingsandvaluesareshownbelow:
InstallationConguration DisplayText Description
Parameters
System Type System Type Short Range
Medium Range
Long Range
Duct Mount
Path Length Path Length 5m min. 200m max. 1m step
0.5m min. 5m max. 0.1m step
APPENDIX A - HANDHELD INTERROGATOR