107
MAN0530 Issue 15 - 07/17 Searchline Excel
2104M0506
B.1 TERMINOLOGY
Ex d
FlameprooforexplosionproofwithintheconnesofEuropeanstandardsEN60079-0and
EN60079-1. An enclosure that can withstand the pressure developed during the internal
explosion of an explosive mixture and that prevents transmission of the explosion to the
explosive atmosphere surrounding the enclosure.
Ex op is
Protection of equipment using Optical Radiation (IEC / EN 60079 – 28). Optical energy
andpowerarelimitedtolevelsthatareincapableofignitingaammableorexplosivedust
atmosphere. The term Ex op is is not to be confused with the term IS described below.
Ex e
IncreasedsafetywithintheconnesofEuropeanstandardsEN60079-0andEN60079-7
applied to electrical apparatus that does not produce arcs or sparks in normal service, in
which additional measures are applied so as to give increased security against the possibility
of excessive temperatures.
Instrument Assisted Alignment (IAA)
A method of commissioning the Excel system using the associated electronic Handheld
Interrogator device. The process will not allow the Excel system to initialise unless the
alignment of the Receiver and Transmitter is correct and the signal strength is correct.
IS
Intrinsically safe, apparatus in which the circuits themselves are incapable of causing ignition
ofaammablegas.
Lower Explosive Limit (LEL)
Thevolumeofammablegasorvapourinairbelowwhichanexplosivegasatmospherewill
not be formed.
RS485
An industry-wide serial communication link protocol.
Turbo heating
Increased Transmitter window heating at low operating temperatures.
B.2 MEASUREMENT UNITS
Open path detectors measure the amount of gas present in the beam. However, they
cannot discriminate between a low concentration gas cloud over a large area and a high
concentration gas cloud in a small area.
APPENDIX B - GLOSSARY