57
MAN0530 Issue 15 - 07/17 Searchline Excel
2104M0506
Faults/Warning
Enter any ACTIVE FAULTS or ACTIVE WARNINGS that could not be cleared from the log,
e.g.
BEAM BLOCK,
E_ZERO_NOT_CALIBRATED
Installation Satisfactory
Only fully trained personnel trained by Honeywell Analytics or Honeywell Analytics authorised
trainers can declare an installation satisfactory. Mark the YES box and sign the form if:
a. having completed the installation and testing, the unit is operating correctly, and
b. in the trained installer's opinion, the unit should continue to operate reliably in this
installation/operatingenvironmentprovidingthatnothingsignicantaboutthe
installation/environment is changed.
If the unit is not operating correctly or there are aspects of the installation/operating
environment which in the trained installer's opinion could or will result in unreliable operation,
mark the NO box.
Reasons for declaring an installation unsatisfactory could include:
excessive movement/vibration of unit’s mounting,
received signal levels too low,
supply voltage too low,
4 - 20mA loop integrity faults,
unclearable active faults,
any prevailing or probable condition which is known to unacceptably reduce
reliability or availability
If Installation is Unsatisfactory, Reasons
Brieystatetheprincipalreasonswhytheinstallationisunsatisfactory,e.g.
Unit mounted on single scaffold pole. Excessive movement,
Beam path obscured by pipes, insufcient received signal levels,
Unit overheated by intense Kuwaiti sunlight
Recommendations
Brieydescribetherecommendedactionswhichneedtobeperformedinordertomakethe
installation satisfactory, e.g.
Mounting pole requires bracing/stiffening,
Pipes obscuring beam to be moved, or detector relocated.
Provide correct supply voltage
Customer Notied
Makesurethattherelevantcustomer/operatorisnotiedoftheinstallationproblem(s).
Mark box accordingly.
System Status
Upon leaving, note the gas detectors status, i.e. operational or nonoperational.
3. INSTALLATION AND OPERATION