8 - 7
MAN0443.P65 Issue 13 Aug 04 5701 Control System
05701-M-5001 A02279
CHAPTER 8 - SPECIFICATION
Measurement Signal Range:
0 to 25mA.
Maximum Line Resistance: 500 ohms loop resistance including
sensor.
Isolation Breakdown
Voltage: More than ±50V dc to system 0V.
5.5 Analogue Output Module
Output Compliance Range: 40V.
Protection: Short circuit protected.
Reverse voltage up to 36V dc.
Transient voltage of less than 60V dc.
Configuration: Isolated current sink.
Isolated current source with external supply.
Signal Range: 0 - 25mA.
Measurement Signal Range:
0 - 20mA or 4 - 20mA selected by the
software.
Linearity From Input: Better than ±2% fsd.
Repeatability From Input: Better than ±1% fsd.
Depending upon the installation, a loss of
performance of less than ±5% fsd may be
observed under extreme conditions of EMC
susceptibility.
Note: The repeatability performance derating is a consequence of the
direct injection test on an installation using unscreened cable
which is part of the EMC testing to Industrial Standards
EN50270:1999.
Isolation Breakdown
Voltage: More than ±50V dc to system 0V.
5.6 Engineering Card
LEDs: Power On ( - Green LED).
Unlocked ( - Red LED).

Table of Contents