MAN0443.P65 Issue 13 Aug 04 5701 Control System
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
Device or Sensor Type Number Unit Total
in Rack Requirement Power
(W) (W)
ABxC=D
System 57 Devices:
Single Channel Control Card,
Catalytic (includes bridge drive
at 200mA) ____ 3.75 ____
Single Channel Control Card,
4-20mA (includes loop power) ____ 3.25 ____
Engineering Card 1 1.50 1.5
DC Input Card 1 0 0
Modbus Interface 232 ____ 0.75 ____
Modbus Interface 422/485 ____ 1.50 ____
Event Printing ____ 0.75 ____
Alarm Update ____ 0.25 ____
Update Panel ____ 0.20 ____
Field Wiring Card ____ 0 0
Relay Card - Double SPCO ____ 0.80 ____
Relay Card - Triple SPCO ____ 1.00 ____
Relay Card - Triple DPCO ____ 1.60 ____
Relay Card - High Integrity ____ 1.70
Analogue Output Module
(excludes loop power) ____ 0.50 ____
Allowance for Transmitters and Sensors powered from System 57 PSU:
Searchline ____ 5.00 ____
Searchline Excel Receiver ____ 8.00 ____
Searchline Excel Transmitter (S/R) ____ 6.50 ____
Searchline Excel Transmitter (L/R) ____ 7.50 ____
Searchline Excel Cross Duct
TX & RX ____ 13.0 ____
Searchpoint 500 ____ 10.00 ____
Searchpoint Optima ____ 4.20 ____
Searchpoint Optima Plus ____ 4.5 ____
Series 2000 Toxic ____ 0 0
Series 2000 Combustible (incl UL) ____ 3.80 ____
Digi-Chem Toxic ____ 0.60 ____
Digi-Cat Combustible ____ 2.00 ____
Digi-Ana Toxic ____ 0.60 ____
Digi-Optima ____ 4.80 ____
Life Line ____ 0 ____
Others (refer to manufacturers
data for column (C) ____ x ____
Apex Toxic* 4.0
Apex Combustible* 5.5
Opus/Lifeline II toxic* 2.4
Opus/Lifeline II combustible* 2.9
TOTAL SYSTEM POWER REQUIREMENT = W