EasyManua.ls Logo

Honeywell CIPer 30 - Page 20

Honeywell CIPer 30
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CIPer
TM
MODEL 30 CONTROLLER - INSTALLATION AND OPERATIONS GUIDE
31-00206 - 02
20
Steps To Perform Provisioning Service
1. Navigate to the ProvisioningNiagara palette, add a new NetworkJobPrototype to any place in the
station under Config (NiagaraNetwork for example) and name the job prototype (example -
CIPer30_1.1.4_Upgrade).
2. Click the (+) icon from Steps run for each station section, select Upgrade Out-of-date Software, and
then click OK.
You can view the list of jobs defined for the required stations.
3. Click the (+) icon from Stations to include in the job section, select the checkbox to select a specific
station, or select the Check All option to select the all listed station, and then click OK.
NOTE
Make sure to increase the Device Reboot Timeout from 10 minutes to 15 minutes if you are
connecting more than 6 expansion IO to the CIPer Model 30 controller.

Other manuals for Honeywell CIPer 30

Related product manuals