DACT-E3 Product Installation Document — P/N 9000-0581:J6 12/16/2019 11
Table 4.2.2.1 lists the DACT-E3 Contact ID Event Reporting Codes for the Custom Formats.
Event
SIA
(See Note 2) Contact ID
4/2
(See Note 3) 3 / 1
(Custom DACT Reporting Formats)
Fire Alarm (Smoke or Manual Station) FA (UUU) 1 110 (NN) (UUU) 0 (U) 0
Fire Alarm Restored FH (UUU) 3 110 (NN) (UUU) 2 (U) 2
Waterflow Alarm Silenceable FA (UUU) 1 110 (NN) (UUU) 0 (U) 0
Waterflow Alarm Non-Silenceable SA (UUU) 1 113 (NN) (UUU) 0 (U) 0
Waterflow Alarm Restored Silenceable FH (UUU) 3 110 (NN) (UUU) 2 (U) 2
Waterflow Alarm Restored Non-Silenceable SH (UUU) 3 113 (NN) (UUU)2 (U)2
CO/Gas Alarm GA (UUU) 1 151 (NN) (UUU) 0 (U) 0
CO/Gas Alarm GH (UUU) 3 151 (NN) (UUU) 2 (U) 2
Trouble (except Waterflow or Special AMM/PID) FT (UUU) 1 373 (NN) (UUU) 8 (U) 8
Trouble Restored FJ (UUU) 3 373 (NN) (UUU) 7 (U) 7
Trouble (Waterflow AMM/PID) ST (UUU) 1 370 (NN) (UUU) 8 (U) 8
Trouble Restored (Waterflow AMM/PID) SJ (UUU) 3 203 (NN) (UUU) 7 (U) 7
Trouble (Special AMM/PID) UT (UUU) 1 370 (NN) (UUU) 8 (U) 8
Trouble Restored (Special AMM/PID) UJ (UUU) 3 370 (NN) (UUU) 7 (U) 7
Supervisory / Tamper (Module) SS (UUU) 1 203 (NN) (UUU) 6 (U) 6
Supervisory Restored (Module) SR (UUU) 3 203 (NN) (UUU) 7 (U) 7
PAS/Action/Supervisory (Sensor) FS (UUU) 1 200 (NN) (UUU) 6 (U) 6
PAS/Action/Supervisory Restored (Sensor) FR (UUU) 3 110 (NN) (UUU) 7 (U) 7
Disable (except Waterflow or Special AMM/PID) FB (UUU) 1 571 (NN) (UUU) 8 (U) 8
Disable Restored FU (UUU) 3 571 (NN) (UUU) 7 (U) 7
Disable (Waterflow AMM) SB (UUU) 1 570 (NN) (UUU) 8 (U) 8
Disable Restored (Waterflow AMM/PID) SU (UUU) 3 570 (NN) (UUU) 7 (U) 7
Disable (Special AMM/PID) UB (UUU) 1 570 (NN) (UUU) 8 (U) 8
Disable Restored (Special AMM/PID) UU (UUU) 3 570 (NN) (UUU) 7 (U) 7
AC Fail AT 0 1 301 (NN) (UUU) 80 8
AC Fail Restored AR 0 3 301 (NN) (UUU) 70 7
Phone Line 1 Fault LT 1 1 351 (NN) (UUU) 81 8
Phone Line 1 Fault Restored LR 1 3 351 (NN) (UUU) 71 7
Phone Line 2 Fault LT 2 1 352 (NN) (UUU) 82 8
Phone Line 2 Fault Restored LR 2 3 352 (NN) (UUU) 72 7
Automatic Test (NORMAL) RP 0 1 602 (NN) (UUU) 90 9
Automatic Test (With Exception) RP 991 1 602 (NN) (UUU) 91 9
Begin Programming LB (900) 1 627 (NN) [900] 90 9
End Programming LX (900) 3 628 (NN) [900] 70 7
E3 Series Releasing (Custom DACT Reporting Formats)
Trouble (Releasing Device) (Supervisory) FS [UUU] 1 200 [NN] [UUU]6 [U]6
Trouble (Releasing Device) (Supervisory Restoral) FR [UUU] 3 200 [NN] [UUU] 7 [U] 7
Pre-Alarm (Action Supervisory) FS [ZZZ] 1 200 [NN] [ZZZ] 6 [Z] 6
Pre-Alarm (Action Restoral) FR [ZZZ] 3 200 [NN] [ZZZ] 7 [Z] 7
Pre-Release (Alarm) FA [ZZZ] 1 110 [NN] [ZZZ] 0 [Z] 0
Pre-Release (Alarm Restoral) FR [ZZZ] 3 110 [NN] [ZZZ] 2 [Z] 2
Release (Alarm) FA [ZZZ] 1 110 [NN] [ZZZ] 0 [Z] 0
Release (Alarm Restoral) FR [ZZZ] 3 110 [NN] [ZZZ] 2 [2] 2
Abort (Supervisory) FS [ZZZ] 1 200 [NN] [ZZZ] 6 [Z] 6
Abort (Supervisory Restoral) FR [ZZZ] 3 200 [NN] [ZZZ] 7 [Z] 7
Manual Dump (Alarm) FA [ZZZ] 1 110 [NN] [ZZZ] 0 [Z] 0
Manual Dump (Alarm Restoral) FR [ZZZ] 3 110 [NN] [ZZZ] 2 [Z] 2
Table 4.2.2.1 DACT-E3 Contact ID Event Reporting Codes for Custom Formats