4.6.2  False Alarm Immunity 
The following table represents the minimum distance at which the detector did not false alarm or show 
any signs of instability during exposure to the sources listed.  Additionally, the sensitivity to a one 
square foot n-Heptane reference pan fire in the presence of the false fire source is listed.   
 
False Fire Source 
Minimum Distance 
with no Alarm 
Sensitivity to a 1' x 1' n-Heptane 
reference pan fire in the 
presence of the false fire source 
Direct Sunlight  No Alarm  50 feet /15.24 meters 
Modulated Sunlight  No Alarm  25 feet / 7.62 meters 
Modulated Arcwelding  3 feet 9 inches / 1.14 meters 
Source at 15 feet / 4.57 meters 
Fire at 30 feet / 9.14 meters 
Continuous Arcwelding  3 feet 9 inches / 1.14 meters 
Source at 15 feet / 4.57 meters 
Fire at 30 feet / 9.14 meters 
Resistive Electric Heater  1 foot / 30.48 centimeters 
Source at 3 feet / 91.44 centimeters 
Fire at 200 feet / 60.96 meters 
Flourescent Lamp  1 foot / 30.48 centimeters 
Source at 3 feet / 91.44 centimeters 
Fire at 200 feet / 60.96 meters 
Halogen Lamp  1 foot / 30.48 centimeters 
Source at 7 feet / 2.13 meters 
Fire at 200 feet / 60.96 meters 
Sodium Vapor Lamp  1 foot / 30.48 centimeters 
Source at 3 feet / 91.44 centimeters 
Fire at 200 feet / 60.96 meters 
Pelican Flashlight  1 foot / 30.48 centimeters 
Source at 3 feet / 91.44 centimeters 
Fire at 200 feet / 60.96 meters 
Incandescent Lamp  1 foot / 30.48 centimeters 
Source at 3 feet / 91.44 centimeters 
Fire at 200 feet / 60.96 meters