12
Weekly tests
Weekly tests
Every week during normal working hours the re detection and alarm 
system should be tested. It is important to inform the alarm receiving centre 
of the re test. 
The weekly re test can be carried out at a manual call point without 
breaking the call point glass. 
  Insert the test key into the keyhole located on the bottom-centre front 
face of the call point and turn the key one quarter of a turn clockwise.
Panel 
buzzer
On
Flashing
Previous Next
Zones
Fault
System Fault
Delay
Test
Fire
Power
Power Fault
Verify
Disablement
Sounder
First Fire occurred at:
Time: 13:43.10  Wed  16  March 2016
1stFIRE:MCP:Zone 1
15:45
1
Manual Call point
Test Key
The ‘Zone indicators’ are not applicable at a Vigilon Plus Network Node
Active
Fault/Dis
Fire
Routing
O/P
If applicable it indicates there is active Fire routing output
to Alarm Receiving Centre. Who would know this is a test
as they would have been advised before the weekly test.
At this point the test key is retained in the call point. 
  Check the alarms are sounding in the building 
and an indication is given of the re event.
  Turn the test key anticlockwise one quarter of 
a turn and remove it from the call point.  
  With the panel door open: 
To cancel 
buzzer
You can stop the panel buzzer from 
sounding.
Press: 
CANCEL
BUZZER
 
Display reads: ‘Buzzer cancelled’
To silence 
alarms
When the test is complete, the alarm 
sounders can be silenced.
Press: 
SILENCE
ALARMS
Display reads: ‘Alarms silenced’
To reset 
system
To return the system to normal 
condition clear any residual smoke 
or heat from sensors and reset 
element or replace the glass in any 
manual call point where the glass 
was broken.
Press:  
RESET
Display reads: 
‘System being Reset - please wait....’
Record 
the event
Make an entry in the log book of the 
event for future reference.