Basics for installing the device in a pipe 
 
HON 380 gas pressure regulator with HON 673/674 controller    24 
 
4.2  Meter run characteristics 
The following recommendations are based on the measuring line connection 
conditions set forth in standards (DIN) EN 334 and (DIN) EN 14382. The com-
pany operating the system is the sole party responsible for the meter run working 
properly. 
 
  A pipe area with a steady flow pattern must be selected for the sensing point. 
There must not be any components that disturb the flow directly upstream 
and downstream of the sensing point, e.g., orifice plates, expanders, bends, 
junctions, shut-off devices, etc. 
  The flow rate at the sensing point should not exceed approx. 25 m/s, de-
pending on the system conditions. 
  In the case of specific system circuits (such as gas regulating lines for gas 
engines) and in the case of gas burners, flow rates higher than 25 m/s may 
be allowed following consultation with the manufacturer. 
  Within a low-pressure range of up to approx. 250 mbar, a maximum flow rate 
of approx. 15 to 20 m/s is recommended at the sensing point. On a case-by-
case basis, and following consultation with the manufacturer, even lower 
flow rates may be allowed. 
 
Depending on the specific system design, the L
uR
 lengths of the undisturbed 
pipes upstream of the sensing point must be (2.5 to 5) x DN of the pipe, with the 
specifics depending on the gas pressure regulator model and whether or not 
there is a pipe expander downstream: 
If …  and...  then... 
A gas pressure regulator 
with an expander that is part 
of the device is used 
The nominal size of the pipe 
is equal to the outlet-side 
nominal size of the gas 
pressure regulator 
L
uR 
min. 2.5 x DN 
The nominal size of the pipe 
is the next larger standard 
nominal size 
L
uR 
min. 3 x DN 
The nominal size of the pipe 
is two standard nominal size 
increments larger 
L
uR 
min. 4 x DN 
The nominal size of the pipe 
is more than two standard 
nominal size increments 
larger 
L
uR 
min. 5 x DN 
A gas pressure regulator 
with the same outlet nomi-
nal size as the inlet nominal 
size is used 
The nominal size of the pipe 
is the next larger standard 
nominal size 
L
uR 
min. 4 x DN 
The nominal size of the pipe 
is two standard nominal size 
increments larger 
L
uR 
min. 5 x DN 
 
basis 
meter run 
sensing point