12 HPF24S Series Power Supplies — P/N 52751:D3 5/11/2010
System Overview Specifications
Wire size: minimum #14 AWG with 600V insulation
Control Input Circuits: TB4, Terminals 3 (+) & 4 (-) and 7 (+) & 8 (-)
Trigger Input Voltage: 9 to 32 VDC
Input Current Draw in Alarm Polarity:
16 to 32 volts, 2.0 mA maximum per input
9 to 16 volts, 1.0 mA maximum per input
NAC/Output Circuits: TB2, Terminals 1 (+) & 2 (-), 3 (+) & 4 (-), 5 (+) & 6 (-) and
7 (+) & 8 (-) alarm polarity
Supervised, Special Application and power-limited
Voltage Rating: 24 VDC filtered
Current:
Maximum for any one circuit - 3.0 amps
Maximum total continuous
current for all output:
HPF24S6 - 4.0 amps
HPF24S8 - 6.0 amps
Maximum total short term
current (one hour maximum) for all outputs:
HPF24S6 - 6.0 amps
HPF24S8 - 8.0 amps
Output Circuit Types:
Four Style Y NACs (require 4.7 KEnd-of-Line Resistors) or
Style Z NACs using the optional ZNAC-4 Class A converter module
OR
Four resettable or nonresettable 24 VDC power outputs
Refer to the Device Compatibility Document for listed compatible devices
For wiring requirements, refer to Appendix A, “Wire Requirements”, on page 42.
Trouble Relay Contact Rating: TB5
Fail-safe Form-C relay (normally energized, transfers with loss of power)
5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC
Secondary Power (battery) Charging Circuit: JP4
Supervised, nonpower-limited
Supports lead acid type batteries only
Float Charge Voltage: 27.6 VDC
Maximum Charge Current: 1.5 A
Battery fuse (F1) 15A, 30V (Candadian version is nonreplaceable 12A, 32V)
Maximum Battery Capacity: 18.0 AH
Minimum Battery Capacity: 7.0 AH
Power supply draws maximum standby current of 65 mA from batteries
Special Application Auxiliary Power Output: TB4 Terminals 9 (+) & 10 (-)
Special application power
Power-limited, nonsupervised
Voltage Rating: 24 VDC
Current:
170 mA maximum with internal 7.0 Amp Hour batteries
500 mA maximum with external 18.0 Amp Hour batteries