l
The antenna should be positioned perpendicularly to the ground, either right side up or upside down.
l
Keep the antenna away from any sources interfering with or blocking the RF signal. For example, a metal object may shield the
cellular radio RF signal. The antenna should be at least 7.8" (20 cm) away from people.
l
The antenna must not be co-located or operating with any other antenna or transmitter.
l
Ensure that the panel supplies 24V DC power from its constant power output.
5.6.2 CONNECTING THE ANTENNA
The antenna comes with an SMA connector, which provides easy connection with the communicator. Connect as follows:
01.
Route the antenna cable through the small rubber grommet located on the top left side of the enclosure as shown in
Mounting the CLSS Pathway into the Enclosure.
02.
Attach the magnet on the bottom of the antenna onto the top wall of the enclosure.
03.
Locate the antenna connector on top of the communicator.
04.
Thread the antenna cable end onto the antenna connector and tighten.
05.
Loop the excess cable length inside the enclosure.
5.7 WIRING THE COMMUNICATOR
The communicator can be wired either for capturing dialer data from a panel’s dialer interface or for monitoring dry contact relay
outputs.
5.7.1 WIRING FOR DIALER CAPTURE
For dialer capture, connect both telephone dialer ports of the fire panel with the communicator. If a dual-path connection is
needed, connect the LAN port of the CLSS Pathway with the customer's network router.
Preparations
l
For panel dialer ports with 8-pin RJ type connectors, use an RJ45 connector with the other end as a pigtail.
l
Use only the Pin 4 wire, which is typically Blue with White stripe, for RING connection.
l
Use only the Pin 5 wire, which is typically solid Blue, for TIP connection.
l
Cut all other wires.
l
Enclosure should be close nipple to the fire alarm control panel.
l
All wirings must be within a conduit.
l
The terminal strips can accommodate solid or stranded wires with sizes from 14 to 22 AWG.
Panel-to-Communicator Wiring
CAUTION: RESETTABLE POWER TERMINALS PROHIBITED
DO NOT USE RESETTABLE POWER TERMINALS.
Honeywell Connected Life Safety Services | Honeywell Connected Life Safety Services
Installation and Operation Manual | REV. B
16