Fire Alarm Control Panel IQ8Control C/M
FB 798951.GB0 / 01.09 101
Type/extent of the detector replacement without
Service-PC *
displayed
trouble code
The type and external switching of the exchanged detector are in
conformance. For example, if a defective OHI-detector without a detector
base output is replaced with a new OHI-detector without a detector base
output.
yes ---
The detector type changes , the external switching remains the same. For
example, an optical smoke detector is replaced with an OHI- detector and
the existing external wiring is not changed.
yes
St : 081-087/
095
During the replacement of detectors, the external switching is removed;
the detector type remains unchanged. For example, an OHI-detector with
a relay output is replaced with an OHI-detector without a relay output. The
change in the external switching from relay to LED outputs (or the
converse) is not recognised.
no St : 088
During the replacement of detectors, the external switching is added, the
detector type remains unchanged. For example, an OHI-detector without a
relay output is replaced with an OHI-detector with a relay output. The
change in the external switching from relay to LED outputs (or the
converse) is not recognised.
yes St : 089
An isolating circuit is removed, the detector type remains unchanged. For
example, an OHI-detector with an isolating circuit (zone isolator) is
replaced with an OHI-detector without an isolating circuit.
no St : 088
An isolating circuit is inserted, the detector type remains unchanged.
yes St : 090
The wiring of the analog loop is changed. For example, during the
replacement of detectors, a new detector is inserted in an additional spur
loop.
no St : 066
Replacement of identical esserbus
®
transponders. A defective esserbus
®
transponder Type 12 relay is replaced with an identical esserbus
®
transponder. The programming of the 12 relay outputs is not changed.
yes ---
Replacement of dissimilar esserbus
®
transponders. An esserbus
®
transponder is replaced by another type or the designation / programming
of the outputs is changed.
no St : 080
Replacement of an esserbus
®
transponder with an automatic detector and
the converse.
no St : 080
Replacement of a manual call point with an esserbus
®
transponder and
the converse.
no St : 080
* Operation without Service-PC available in the installer level of the Fire Alarm Control Panel IQ8Control C/M.