EasyManuals Logo
Home>Honeywell>Control Panel>IQ8Control C

Honeywell IQ8Control C User Manual

Honeywell IQ8Control C
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
Fire Alarm Control Panel IQ8Control C/M
FB 798951.GB0 / 01.09 85
Assignment of terminal card RS232 module
1
2
3
4
5
6
7
8
not used
RxD (receive)
Data GND (potential free)
TxD (transmitt)
RxD
TxD
Data
GND
external device
not used
not used
not used
not used
Fig. 75: Assignment of terminal card RS232 module
Max. cable length for RS 232 is 15 m, recommended cable: I-Y (St) Y x 2 x 0.8mm
Assignment for terminal card TTY module
1
2
3
4
5
6
7
8
not used
Tx -
Rx +
Tx +
Rx -
transmitt
receive
transmitt
Rx -
Tx +
Rx +
Tx -
external device
not used
not used
not used
receive
Fig. 76: Assignment for terminal card TTY module
If solder jumper BR3 is closed on the module, TTY interface may not be used.
Max. cable length for TTY is 1000 m, recommended cable: I-Y (St) Y x 2 x 0.8mm