EasyManua.ls Logo

Honeywell MiniZone EMM-3U - Sequence of Operation

Honeywell MiniZone EMM-3U
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EMM-3U UNIVERSAL ELECTRONIC MINIZONE™ PANEL
68-0237-2 12
Sequence of Operation
When there is no call for heat, cool, or fan, the EMM-3U is
in the Idle mode. No system LEDs are illuminated and the
damper LEDs are green to indicate open.
On a call for heat, cool, or fan, the calling zone damper
stays open, and the other zone dampers close:
Panel energizes the HVAC equipment and conditioned
air is delivered to the calling zone.
Heat LED (red), cool LED (green), or fan LED (green)
illuminates to indicate equipment operation.
Fan LED illuminates only during a call for circulation; it
does not illuminate during a call for heat or cool.
When the call is satisfied, the system enters the Purge
mode. After Purge, all dampers return to the Open position
Any zone thermostat can call for heating or cooling. If there
are co-existing calls for heat and cool, the panel accepts
the first call.
Once a call is satisfied, or a maximum of 20 minutes has
elapsed, the panel switches to allow the opposite call after
completing Purge mode.
Purge Mode
At the end of every call for heat or cool, the panel enters a
Purge mode that holds open the calling zone damper for
two minutes (default) or three and one-half minutes.During
this time, the panel or the HVAC equipment can be
configured to operate the fan.
The Purge LED lights to signal that the system is in the
Purge mode. Pressing the purge override button overrides
the Purge mode.
Unless there is a new call for heat or cool during the Purge
mode, all dampers are moved to the Open position at the
end of Purge.
The panel can be configured to open all dampers during
purge mode.See Table 4 to configure the Purge mode
using DIP switches 8, 9 and 10.
Individual Zone Fan Control
The fan switch of each thermostat controls the fan
operation for that zone.
When the Fan switch is in the On position, the fan is
energized, and dampers close to zones where the Fan
switch is in Auto position.
During a call for heat or cool at this time, the circulation
mode ceases, and the heat or cool call is honored.
When the zone calling is satisfied, the circulation call
resumes.
Single- and Multi-Stage Operation
The panel can control up to two stages of heat and cool:
First stage is energized by the thermostat
Second stage of heating or cooling can be energized by
the thermostat or timer.
Single-Stage
Select a single stage thermostat, see Table 1. Set DIP
switches 1, 2, and 3 to Off to disable the stage timer.
Multi-Stage
THERMOSTAT-CONTROLLED STAGES
Select a multi-stage thermostat, see Table 1, that
energizes W2 and Y2 for second stage of heat and cool.
Configure DIP switches 1, 2 and 3 to Off to disable the
stage timer.
Timer Controlled Stages
The panel stage timer energizes the second stage of heat
or cool after the first stage has been calling for a specified
amount of time.
Second stage remains energized until the call for heat or
cool is satisfied.
See Table 5 for stage timer configuration.
Heat Pump Operation
The panel can control single or two stage heat pumps with or
without auxiliary heat:
Set DIP switch 4 to Off for heat pump control. This
energizes the Y1 on a call for first stage heat or cool.
Set DIP switch 7 to Off to engage the fan with a call for
heat.
Thermostat Controlled Stages
Select a thermostat from Table 1. Configure DIP switches
1,2, and 3 to off to disable the stage timer.
When thermostat calls for first stage, panel energizes
Y1, G and the correct reversing valve terminal.
When the thermostat calls for second stage heat on
W2, the panel energizes the equipment W2 terminal.
Recommended heat pump thermostats can switch the
panel to emergency heat:
In this mode, Y1 equipment terminal is disabled and E
is energized on a call for heat.
If the same source of heat is used for emergency heat
and auxiliary heat, W2 and E equipment terminals
must be jumpered.
Emergency heat can be energized by the Em Heat switch
on the panel.
If the equipment is a two-stage heat pump, W2 and Y2
equipment terminals must be jumpered and wired to the
second stage compressor contactor.
If the equipment is a two-stage heat pump with auxiliary
heat, select the TZ-4 TotalZone™ panel.
Timer Controlled Stages
If single-stage thermostats are used, the EMM-3U can
energize second stage using stage time:
The timer can be set to engage second stage heat or cool
after the first stage has been calling for the specified length
of time.
See Table 5 for DIP switch configuration.
Thermostat Operation
Conventional Thermostats
Conventional (R,W,Y,G) heat/cool thermostats can be used
with the EMM-3U to control single or multi-stage gas, electric,
or oil systems and heat pumps with or without auxiliary heat.
For two stage heat or cool equipment, configure the stage
timer with DIP switches 1, 2 and 3. See Table 5. This
enables the panel to engage second stage after stage one
has been calling for the specified length of time.

Related product manuals