EMM-3U UNIVERSAL ELECTRONIC MINIZONEā„¢ PANEL
68-0237-2 14
Table 4. DIP Switch Settings and Functions.
DIP Switch Function On (Default) Off
1 Stage Timer See Table 5.
2 Stage Timer See Table 5.
3 Stage Timer See Table 5.
4 System Type Conventional Heat Pump
5 DATS High Limit 160 120
6 DATS Low Limit 40 48
7 Heat Fan HVAC controls fan in heat Panel engages fan in heat
8 Purge Fan Purge Fan controlled by
HVAC
Panel engages Purge Fan.
9 Purge Damper Purges into last zone calling Purges into all zones
10 Purge Time Two minutes 3-1/2 minutes
11 EM Heat Fan HVAC controls fan in EM
heat
Panel engages fan with heat
12
2
nd
Stage Em Heat
Yes No
Table 5. Stage Timer Configuration.
Time (Minutes) DIP Switch 1 DIP Switch 2 DIP Switch 3
5 On On On
10 On On Off
15 On Off On
20 On Off Off
30 Off On On
45 Off On Off
60 Off Off On
No Timer Off Off Off