8.4 Menu Measuring Values
In this menu, the display shows the measuring value with gas type and unit. If the alarm evaluation is defined
via the average, the display additionally shows the average value (A) to the left of the current value (C).
Selection of the next measuring point
Analog measuring point 1 to 3
Digital measuring point 4 to 11
Display of gas type (must comply with gas type of sensor head)
Unit (depending on gas type)
C = Current measured value (current value) of the gas concentration
A = Arithmetic average of the gas concentr. (only if average is active)
At least one alarm has been released at this MP.
Sensor head: maintenance due (maintenance date exceeded)
Communication error, sensor head <> I/O board
Meas. signal < admissible range (< zero point – 6 %)
Meas. signal > admissible range (> full scale value + 6 %)
Warm-up of the sensor active
1
Display of the address number the measuring range is registered under in the Modbus
2
Acknowledgement in the menu Alarm Status
8.5 Display Parameters
In the menu Display Parameters, you can find the general, non-safety related parameters of the display. These
parameters can be changed in operating mode.
8.5.1 Software Version
Software version of the display and of the basic board
Software Version of the displays
Software Version of the basic board
XXXXX Software Version
YYYYY Software Version
Software Version
XXXXX - YYYYY