= Relay manually set in alarm status
= Relay manually set in “no alarm“ status
= Reset of manual intervention, relay
in automatic mode
8.11 Test Function for Analog Output
In this menu, you can define a desired value in mA for the analog output in order to test its function. This value
is then directly available at the output.
This menu is only available in special mode.
The manual operation has priority over the activation by the gas concentration.
The testing is possible via code level 1, 3 and 4.
When the menu is exited, the actual current signal is immediately output again, the entry field shows 0.
The test function is only possible for an active analog output.
On the left you can see the current set-point
as calculated from the gas concentration.
Enter the required current under “Set Value”,
e.g. 12 mA
The set value is accepted as set-point
(by displaying it on the left)
and is physically output.