Display Unit for Series MGC2-K
5 Intended Use for the Display Unit
The display is used as visual indication, operating, commissioning and calibration unit for gas detecting and
measuring instruments of the series PolyGard
®
2 (PG2).
6 Description
The parameters, gas types, units, etc. specified in the description are only examples.
7 Operation
The complete configuration and service are made via operating keys in combination with the LCD display
screen. Security is provided via four password levels against unauthorized intervention
Version for PG2 series
Operation via 6 buttons
7.1 Function of the Keys and LEDs on the Keypad
Exits programming, returns to the previous menu level.
Enters sub menus, saves parameter settings.
Scrolls up & down within a menu, changes a value.
Changes cursor position.
The status LEDs indicate the operating state.
Green: Continuous: = Normal operation
Flashing: = Maintenance message
Yellow: Continuous: = Failure
Slowly flashing: = Warming-up
Fast flashing: = Special mode
Red: =Alarm
The backlight of the display changes from green to red when an alarm is active.