8.6.7 Delay Mode of Alarm Relay
.
Relay 3:
The parameter setting cannot be changed.
Definition of the time for switch-on and switch-off delay of the alarm relays.
Symbol
Description
Default
Function
0 sec.
Switch-ON
Delay Time
0
≥ 1: Alarm relay is only activated at the end of the defined time.
0 = No delay
0 sec.
Switch-OFF
Delay Time
0
≥ 1: Alarm relay is only deactivated at the end of the defined time.
0 = No delay
8.6.8 Assignment to Fault
Relay 3:
The parameter setting cannot be changed.
In case of a device fault the alarm, relay is triggered in addition.
This relay output must not be used as a safe error output.
Symbol
Description
Default
Function
No
No assignment
No
Alarm relay is not activated in case of a device fault.
Yes
Assignment to
fault
Yes
Alarm relay is activated in case of a device fault.
8.6.9 Assignment to Maintenance Message
In case of a pending maintenance, the alarm relay is triggered in addition.
Symbol
Description
Default
Function
No
No assignment
No
Alarm relay is not activated in case of a maintenance message.
Yes
Assignment to
maintenance
Yes
Alarm relay is activated in case of a maintenance message.
On Delay Time
0 s
Off Delay Time
0 s
Maintenance Active
No
Fault Active
No