ID2000 Series Operating Manual
Operator Actions at Panel
19 997-434-000-4, Issue 4
May 2010
4 The system displays one of the prompts shown below
(depending upon whether the module is currently
active or not):
5 Press
to perform the test. Once in test mode, the
following prompt is displayed:
Pressing X will abandon the testing of that particular
module. You are then prompted with:
If required, enter other modules for testing using the
!" keys (or enter the exact, or approximate, number
of the module). To finish testing, pressing the
key
a number of times will take you back to the Top Level
menu.
To switch off the module quickly, simply press SILENCE
SOUNDERS. However, if you do not want to silence
sounders elsewhere, i.e. you want them to remain on
because of an Alarm or Evacuate condition, or if the
module is non-silenceable you will have to repeat the
above sequence and press
to stop the test.
4.8.2.2 Local Sounder Circuits
To test one of the four local sounder circuits:
1 Press 1, 2, 3 or 4 in response to the options shown in
Section 4.8.2. The system displays one of the
questions shown below (depending upon whether the
sounder is currently active or not):
2 Press
to perform the test. To switch off the sounder
quickly, simply press SILENCE SOUNDERS. However,
if you do not want to silence sounders elsewhere, i.e.
you want them to remain on because of an Alarm or
Evacuate condition, you will have to repeat the sequence
above. If circuit 3 or 4 is configured as a relay, SILENCE
SOUNDERS will not affect it and the sequence above
must be repeated. Pressing the panel RESET
pushbutton will return all active outputs to normal.
Mod. (n) - Zone (n) - (type)
Switch Module ON (
!!
!!
!/X)?
Mod. (n) - Zone (n) - (type)
Switch Module OFF (
!!
!!
!/X)?
Switch Sounder n ON (
!!
!!
!/X)?
Switch Sounder n OFF (
!!
!!
!/X)?
Switch Relay n ON (
!!
!!
!/X)?
Switch Relay n OFF (
!!
!!
!/X)?
Use
↑↑
↑↑
↑
↓↓
↓↓
↓ to step up/down,
!!
!!
! to select
Press X to terminate test _