ID2000 Series Operating Manual
Automatic Alarms - What to do
6997-434-000-4, Issue 4
May 2010
3.3 Fault
Automatic panel actions - If the system identifies a fault,
the panel always does the following automatically:
a. Operates the internal FAULT buzzer.
b. Flashes one or more amber FAULT lamps, including
numbered amber ZONE Fault lamp(s) if appropriate.
c. Operates any control outputs which are associated
in the Control Matrix with fault events.
d. Displays and prints (if printer is installed and enabled)
information about the event.
Note: For a sensor fault, only the point of origin or a brief
reference appears on the text display.
e. Operates the fault transfer relay (for automatic alert
to a service centre).
Recommended operator actions:
1 Press the ACCEPT pushbutton. More information
about the fault appears on the display. Flashing lamps
change to steady operation. The internal fault sounder
changes to intermittent operation (once every
2 minutes).
2 If the fault relates to a specific sensor or module,
investigate device to see if cause of fault is
immediately apparent and can be corrected.
3 In all other cases, note full description of fault and
notify authorised Servicing company.
4 When cause of fault has been cleared, press the
RESET pushbutton.
Note: If the scrolling or static display messages are difficult
to read, adjust the display contrast (see
Section 4.7.2).