ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
41
997-263-000-11, Issue 11
January 2010
1
5.5.1.3 Control Keys Access Level
EN54-2 requires the following access to controls:
Level 2: Reset (EN54-2 Clauses 7.6.1 & 8.7.1)
Silence Sounders (EN54-2 Clause 7.8)
Extend Delays (EN54-2 Clause 9.1.2)
Level 1: End Delays (or MCP) (EN54-2 Clause 7.11d).
The Control Keys option allows the access level at which
the panel control keys can be operated to be changed.
To select the required access level:
1 From the Setup menu screen, using the numeric
keypad press the ‘
1
button to enter the Panel
Options menu. The Language screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Panel
Options menus until the Control Keys screen is
displayed.
3 Press the ‘
6
’ button to change the setting to level 1
(no passcode) or level 2 (user passcode). The default
access level is level 2.
4 Press ‘
4
to return to the Setup menu screen. All
changes will be saved on exiting.
5.5.1.4 LED 1H Mode
The default function for this LED is PLANT ALARM. This option
allows this LED on panels with the new 5-button membrane
to be configured as FAULT O/P: FAULT/DISABLED.
1 From the Setup menu, using the numeric keypad press
the ‘
1
button to enter the Panel Options menu. The
Language screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Panel
Options menus until the LED 1H Mode screen is
displayed.
[Setup] Control Keys Access Level = 2
> : Change ¦ : More < : Exit
[Setup] Language = English
> : Change ¦ : More < : Exit
or
82
EN54-2 : 7.6.1, 7.8, 8.7.1,
9.1.2
Ensure EN54 compliance
for access to controls.
PLANT ALARM
FAULT O/P: FAULT / DISABLED
DISABLEMENT
FAULT
TEST
POWER SUPPLY FAULT
EARTH FAULT
POWER
FIRE OUTPUT ACTIVE
DELAYS ACTIVE
FIRE OUTPUT: FAULT / DISABLED
FIRE CONTROL O/P: FAULT / DISABLED
PRE- ALARM
SYSTEM FAULT
SOUNDER: FAULT / DISABLED
1
or
8
2
[S1 Setup] 4: Peripheral Options
5: Day / Night Settings ¦ : More
[S1 Setup] 1: Panel Options
2: Site Details 3: Device Options ¦ : More
[Setup] Language = English
> : Change ¦ : More < : Exit
[Setup] LED 1H = Plant Alarm
> : Change ¦ : More < : Exit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals