ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
48
997-263-000-11, Issue 11
January 2010
[Setup] Auto High Test = DISABLED
> : Change 1 : Disable ¦ : More < : Exit
[Setup] Auto High Test = 07:46
> : Change 1 : Disable ¦ : More < : Exit
1
To disable this function
1 To disable Auto High Test, press the ‘
1
button:
2 Press ‘
4
’ to return to the Setup menu screen.
5.5.3.4 Digital Input 1
Digital Input 1 can be configured as either Day Mode Start
or Class Change function.
When configured as Day Mode Start, activation from the
input during the Day Mode period starts/ends Day Mode
delays, depending on their current state.
When Class Change is selected outputs assigned to CBE
Rules that have Class Change configured will activate
when Digital Input 1 is operated.
To configure Digital Input 1:
1 Using the numeric keypad, press ‘
3
at the Setup
menu screen to enter the Device Options screen. The
Device blinking screen is displayed first.
2 Press either ‘
2
/
8
’ to step through the Device
Options until the Digital Input 1 menu is displayed.
3 Press ‘
6
to toggle between Day Mode Start and
Class Change.
4 With the required configuration of Digital Input 1
displayed, press ‘
4
’ to return to the Setup menu screen.
5.5.3.5 Maximum LEDs ON
The maximum number of LEDs turned on in alarm or
fault conditions can be set to 10 or 2. Fire takes priority;
a fault LED will be turned off to allow a fire LED to be
turned on if the LED maximum has been reached.
[Setup] Digital Input 1 = Day Mode Start
> : Change ¦ : More < : Exit
[Setup] Digital Input 1 = Class Change
> : Change ¦ : More < : Exit
[Setup] Device Blinking = ON
> : Change ¦ : More < : Exit
3
or
8
2
6
[Setup] Max. LEDs ON = 10
> : Change ¦ : More < : Exit
Press ‘
6
’ to toggle between 10 (default) and 2 or press
4
’ to return to the Setup menu screen.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals