EasyManuals Logo

Honeywell Notifier ID50 User Manual

Honeywell Notifier ID50
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
49
997-263-000-11, Issue 11
January 2010
5.5.3.6 Day Mode Sensitivity
This option allows a change in sensor sensitivity to be set
during the same period each day (including weekends unless
Weekend Night Mode is enabled). Refer to Section 5.6.1.2
Sensor Sensitivity Setting for day mode sensitivity setting.
Day mode start and end times need to be specified as follows:
1 From the Device options menu, press either ‘
2
/
8
to step through the Device Options until the Day Mode
Sensitivity screen is displayed.
2 Press ‘
6
to enter a start time (using the 24hr clock):
3 Press the ‘
5
button to confirm the start time. You
are now prompted to enter an end time:
Press the ‘
5
button to confirm the finish time. The day
mode start and end times are now displayed:
Press either ‘
2
/
8
’ to select another device option or
press ‘
4
’ to return to the Setup menu screen.
5.5.3.7 Weekend Night Sensitivity
If Weekend Night Sensitivity is enabled, the panel
disregards the Day Mode Sensitivity period on the two
days of the week that coincide with the weekend. To set
this mode active:
1 From the Setup menu screen, press the ‘
3
’ button
on the numeric keypad to enter the Device Options
menu. The Device Blinking screen is displayed first.
2 Use ‘
2
/
8
’ to scroll through the device options until
Weekend night Sensitivity is displayed:
3 Press ‘
6
’ to toggle between ENABLED and DISABLED.
Press either ‘
2
/
8
’ to select another device option or
press ‘
4
’ to return to the Setup menu screen.
[Setup] Day Mode Sensitivity = DISABLED
Enter Finish time: 17:00 < : Cancel
[Setup] Day Mode Sensitivity = DISABLED
Enter Start time: 08:00 < : Cancel
[Setup] Day Mode Sensitivity = DISABLED
> : Change 1: Disable ¦ : More < : Exit
[Setup] Day Mode Sensitivity = 08:00
-
>17:00
> : Change 1: Disable ¦ : More < : Exit
[Setup] Weekend night Sens. = ENABLED
> : Change ¦ : More < : Exit
[Setup] 1: Panel Options
2: Site Details 3: Device Options ¦ : More
[Setup] Device Blinking = ON
> : Change ¦ : More < : Exit
or
82
5
6
5
3
or
8
2

Table of Contents