ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
50
997-263-000-11, Issue 11
January 2010
[Setup] Ext. System Soak = 0 Seconds
> : Change ¦ : More < : Exit
3
or
8
2
6
[Setup] Device Blinking = ON
> : Change ¦ : More < : Exit
5.5.3.8 Extinguishing System Delay
The extinguishing system delay allows an evacuation period
of up to 180 seconds to be entered (default 60 secs, minimum
of 10 secs). To configure the delay, proceed as follows:
1 From the Setup menu screen, press the ‘
3
’ button on
the numeric keypad to enter the Device Options menu.
The Device blinking screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Device
Options until the Ext. System Delay screen is
displayed. Press the ‘
6
’ button to change the delay
time. The display then prompts you for the new value:
3 Enter the required delay time using the numeric
buttons, e.g. 30 secs:
4 Press the ‘
5
’ button to confirm and return to the
Setup menu screen.
5.5.3.9 Extinguishing System Soak
To specify for how long the extinguishing system operates
after being turned on:
Note: The timer will only be triggered by CBE rules that
have the Soak Timer Enable activated.
1 From the Setup menu screen, press the ‘
3
’ button on
the numeric keypad to enter the Device Options menu.
The Device blinking screen is displayed first.
2 Press the ‘
2
/
8
’ buttons to step through the Device
Options to display the Ext. System Soak screen.
3 Press the ‘
6
button. The display then prompts you
for the new value:
[Setup] Ext. System Soak = 0 Seconds
Enter new value __ : Confirm < : Cancel
[Setup] Ext. System Delay = 60 Seconds
Enter new value 30 : Confirm < : Cancel
6
or
8
2
[Setup] Ext. System Delay = 60 Seconds
Enter new value __ : Confirm < : Cancel
[Setup] 1: Panel Options
2: Site Details 3: Device Options ¦ : More
[S1 Setup] 1: Panel Options
2: Site Details 3: Device Options ¦ : More
3
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
[Setup] Device Blinking = ON
> : Change ¦ : More < : Exit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals